CLASSIFICATION OF GENERAL VENTILATION FILTERS ACCORDING TO THE EN 779:2002 NORM
Filter class according to EN 779:2002
Average gravimetric efficiency
Average colorimetric efficiency
Filter class
according to UNI 10339
Filter efficiency
according to UNI 10339
Am %
Em %
G1
Am < 65
 
1
M
G2
65 ≤ Am ≤ 80
 
2
M
G3
80 ≤ Am ≤ 90
 
3
M
G4
90 ≤ Am
 
4
M
F5
 
40 ≤ Em ≤ 60
5
A
F6
 
60 ≤ Em ≤ 80
6
A
F7
 
80 ≤ Em ≤ 90
7
A
F8
 
90 ≤ Em ≤ 95
8
A
F9
 
95 ≤ Em
9
A



CLASSIFICATION OF HEPA FILTERS ACCORDING TO THE EN 1822 NORM
M.P.P.S. global values
M.P.P.S. local values
Filter class
Efficiency (%)
Penetration (%)
Efficiency (%)
Penetration (%)
H10
85
15
   
H11
95
5
   
H12
99,5
0,5
   
H13
99,5
0,05
99,75
0,25
H14
99,995
0,005
99,975
0,025
U15
99,9995
0,0005
99,9975
0,0025
U16
99,99995
0,00005
99,99975
0,00025
U17
99,999995
0,000005
99,9999
0,0001



CLASSIFICATION OF HEPA FILTERS ACCORDING TO THE EUROVENT 4/4 NORM
Filter class according to Eurovent 4/4
Initial efficiency
Penetration
Filter class
according to UNI 10339
Filter efficiency
according to UNI 10339
Ei %
P %
EU10
95 ≤ Ei < 99,9
5 ≥ P > 0,1
10
AS
EU11
99,9 ≤ Ei < 99,97
0,1 ≥ P > 0,03
11
AS
EU12
99,97 ≤ Ei < 99,99
0,03 ≥ P > 0,01
12
AS
EU13
99,99 ≤ Ei < 99,999
0,01 ≥ P > 0,001
13
AS
EU14
99'999 ≤ Ei
0,001 ≥ P
14
AS



CAIR PURITY CLASSES FOR PARTICLES ACCORDING TO THE FED. STD 209E NORM
Air purity class
Max particles concentration per m3
International system
English units
0,1 µm
0,2 µm
0,3 µm
0,5 µm
5 µm
M 1
 
350
75,7
30,9
10
 
M 1,5
1
1240
265
106
35,5
 
M 2
 
3500
757
309
100
 
M 2,5
10
12400
2650
1060
353
 
M 3
 
35000
7570
3090
1000
 
M 3,5
100
 
26500
10600
3530
 
M 4
   
75700
30900
10000
 
M 4,5
1000
     
35300
247
M 5
       
100000
618
M 5,5
10000
     
353000
2470
M 6
       
1000000
6180
M 6,5
100000
     
353000
24700
M 7
       
10000000
61800



FILTER USE IN VENTILATION PLANTS IN ACCORDANCE WITH THE UNI 10339 NORM
Building classification into
Filter class
Filter
efficiency
UNI 10339
Min.
Max.
BUILDINGS FOR RESIDENTIAL PURPOSE AND THE LIKE      
Houses, colleges, warehouses and storage places
4
7
M*, M+A
Penitentiaries, barracks, cloisters
4
7
M*, M+A
Hotels, boarding houses
5
7
M+A
OFFICE PERMISES AND THE LIKE      
Officies in general
5
7
M+A
Meeting rooms
5
7
M+A
Data Processing centres
6
9
M+A
HOSPITALS, CLINICS, NURSING HOMES AND THE LIKE      
Hospitalisation (2-3 beds) , wards
6
8
M+A
Sterilised and infective rooms
10
11
M+A+AS
Maternity ward, anaesthesia ward, radiology
10
11
M+A+AS
Premature babies ward, operating rooms
11
12
M+A+AS
Out-patients' departments, visits
6
8
M+A
Stays, physical therapies
6
8
M+A
RECREATIONAL, SOCIALIZING AND RELIGIOUS BUILDINGS      
Cinemas, theatres, conference rooms
5
6
M+A
Museums, libraries
7
9
M+A
Worship places
4
6
M*, M+A
Restaurant bars, ballrooms
3
5
M*, M+A
Dining rooms, restaurants
5
6
M+A
Dance halls
3
5
M*, M+A
Kitchens
2
4
M
BUSINESS ACTIVITIES AND THE LIKE      
Department stores, shops in general
4
6
M*, M+A
Grocers'
5
6
M*, M+A
Photographers' and chemists'
5
6
M+A
Waiting areas in banks
4
6
M*, M+A
Fair Grounds
2
3
M
BUILDINGS FOR SPORT ACTIVITIES      
Swimming pools, saunas and the like
4
6
M*, M+A
Gymnasiums and the like
2
4
M
BUILDING FOR SCHOLASTIC ACTIVITIES      
Kindergardens and primary schools
7
9
M+A
Classrooms in general
5
6
M+A
Music and language laboratoires
6
7
M+A
Laboratoires in general
6
7
M+A

(*) To employ up to class 4 of filter efficiency