CLASSIFICATION OF GENERAL VENTILATION FILTERS
ACCORDING TO THE EN 779:2002 NORM
Filter
class according to EN 779:2002 |
Average
gravimetric efficiency |
Average
colorimetric efficiency |
Filter
class
according to UNI 10339 |
Filter
efficiency
according to UNI 10339 |
Am % |
Em % |
G1 |
Am
< 65 |
|
1 |
M |
G2 |
65 ≤ Am ≤
80 |
|
2 |
M |
G3 |
80
≤ Am ≤ 90 |
|
3 |
M |
G4 |
90 ≤ Am |
|
4 |
M |
F5 |
|
40
≤ Em ≤ 60 |
5 |
A |
F6 |
|
60 ≤ Em ≤
80 |
6 |
A |
F7 |
|
80
≤ Em ≤ 90 |
7 |
A |
F8 |
|
90 ≤ Em ≤
95 |
8 |
A |
F9 |
|
95
≤ Em |
9 |
A |
CLASSIFICATION OF HEPA FILTERS ACCORDING
TO THE EN 1822 NORM
M.P.P.S.
global values |
M.P.P.S.
local values |
Filter class |
Efficiency (%) |
Penetration (%) |
Efficiency (%) |
Penetration (%) |
H10 |
85 |
15 |
|
|
H11 |
95 |
5 |
|
|
H12 |
99,5 |
0,5 |
|
|
H13 |
99,5 |
0,05 |
99,75 |
0,25 |
H14 |
99,995 |
0,005 |
99,975 |
0,025 |
U15 |
99,9995 |
0,0005 |
99,9975 |
0,0025 |
U16 |
99,99995 |
0,00005 |
99,99975 |
0,00025 |
U17 |
99,999995 |
0,000005 |
99,9999 |
0,0001 |
CLASSIFICATION OF HEPA FILTERS ACCORDING
TO THE EUROVENT 4/4 NORM
Filter
class according to Eurovent 4/4
|
Initial
efficiency |
Penetration |
Filter
class
according to UNI 10339 |
Filter
efficiency
according to UNI 10339 |
Ei % |
P % |
EU10 |
95
≤ Ei < 99,9 |
5
≥ P > 0,1 |
10 |
AS |
EU11 |
99,9 ≤ Ei <
99,97 |
0,1 ≥ P >
0,03 |
11 |
AS |
EU12 |
99,97
≤ Ei < 99,99 |
0,03
≥ P > 0,01 |
12 |
AS |
EU13 |
99,99 ≤ Ei <
99,999 |
0,01 ≥ P >
0,001 |
13 |
AS |
EU14 |
99'999
≤ Ei |
0,001
≥ P |
14 |
AS |
CAIR PURITY CLASSES FOR PARTICLES ACCORDING
TO THE FED. STD 209E NORM
Air purity
class |
Max particles
concentration per m3 |
International system |
English units |
0,1 µm |
0,2 µm |
0,3 µm |
0,5 µm |
5 µm |
M
1 |
|
350 |
75,7 |
30,9 |
10 |
|
M 1,5 |
1 |
1240 |
265 |
106 |
35,5 |
|
M
2 |
|
3500 |
757 |
309 |
100 |
|
M 2,5 |
10 |
12400 |
2650 |
1060 |
353 |
|
M
3 |
|
35000 |
7570 |
3090 |
1000 |
|
M 3,5 |
100 |
|
26500 |
10600 |
3530 |
|
M
4 |
|
|
75700 |
30900 |
10000 |
|
M 4,5 |
1000 |
|
|
|
35300 |
247 |
M
5 |
|
|
|
|
100000 |
618 |
M 5,5 |
10000 |
|
|
|
353000 |
2470 |
M
6 |
|
|
|
|
1000000 |
6180 |
M 6,5 |
100000 |
|
|
|
353000 |
24700 |
M
7 |
|
|
|
|
10000000 |
61800 |
FILTER USE IN VENTILATION PLANTS IN ACCORDANCE
WITH THE UNI 10339 NORM
Building classification into |
Filter class |
Filter
efficiency |
UNI 10339 |
Min. |
Max. |
| BUILDINGS FOR RESIDENTIAL PURPOSE AND
THE LIKE |
|
|
|
| Houses, colleges, warehouses and storage places |
4 |
7 |
M*, M+A |
| Penitentiaries, barracks, cloisters |
4 |
7 |
M*, M+A |
| Hotels, boarding houses |
5 |
7 |
M+A |
| OFFICE PERMISES AND THE LIKE |
|
|
|
| Officies in general |
5 |
7 |
M+A |
| Meeting rooms |
5 |
7 |
M+A |
| Data Processing centres |
6 |
9 |
M+A |
| HOSPITALS, CLINICS, NURSING HOMES AND
THE LIKE |
|
|
|
| Hospitalisation (2-3 beds) , wards |
6 |
8 |
M+A |
| Sterilised and infective rooms |
10 |
11 |
M+A+AS |
| Maternity ward, anaesthesia ward, radiology |
10 |
11 |
M+A+AS |
| Premature babies ward, operating rooms |
11 |
12 |
M+A+AS |
| Out-patients' departments, visits |
6 |
8 |
M+A |
| Stays, physical therapies |
6 |
8 |
M+A |
| RECREATIONAL, SOCIALIZING AND RELIGIOUS
BUILDINGS |
|
|
|
| Cinemas, theatres, conference rooms |
5 |
6 |
M+A |
| Museums, libraries |
7 |
9 |
M+A |
| Worship places |
4 |
6 |
M*, M+A |
| Restaurant bars, ballrooms |
3 |
5 |
M*, M+A |
| Dining rooms, restaurants |
5 |
6 |
M+A |
| Dance halls |
3 |
5 |
M*, M+A |
| Kitchens |
2 |
4 |
M |
| BUSINESS ACTIVITIES AND
THE LIKE |
|
|
|
| Department stores, shops in general |
4 |
6 |
M*, M+A |
| Grocers' |
5 |
6 |
M*, M+A |
| Photographers' and chemists' |
5 |
6 |
M+A |
| Waiting areas in banks |
4 |
6 |
M*, M+A |
| Fair Grounds |
2 |
3 |
M |
| BUILDINGS FOR SPORT ACTIVITIES |
|
|
|
| Swimming pools, saunas and the like |
4 |
6 |
M*, M+A |
| Gymnasiums and the like |
2 |
4 |
M |
| BUILDING FOR SCHOLASTIC ACTIVITIES |
|
|
|
| Kindergardens and primary schools |
7 |
9 |
M+A |
| Classrooms in general |
5 |
6 |
M+A |
| Music and language laboratoires |
6 |
7 |
M+A |
| Laboratoires in general |
6 |
7 |
M+A |
(*) To employ up to
class 4 of filter efficiency
|